Sun Pharmaceuticals, India
In brief. Heat from three Deutz engines is split between two Thermax chillers and a steam boiler; process cooling is about 2,500 kW.

At the Sun Pharmaceuticals plant, three 1.4 MW engines run on gas. The exhaust and jacket water drive two Thermax absorption chillers, and a heat recovery steam generator produces steam separately. Total cooling is about 2,500 kW of process cooling.
What does the project consist of?
| Parameter | Value |
|---|---|
| Industry | Pharmaceuticals |
| Engines | 3 Deutz (MWM) engines, 1.4 MW each |
| Fuel | Natural gas |
| Heat for the chiller | Exhaust at 527 and 478 °C, jacket water at 90 °C, plus a heat recovery steam generator producing 2,917 kg of steam per hour |
| Chiller and cooling | 2 chillers: 1,652 kW (470 TR) and 844 kW (240 TR) |
| What the cooling is for | Process cooling |
Why is this example useful for a Russian site?
Three 1.4 MW engines give 2,496 kW of cooling, about 0.6 kW per kW of electricity: part of the exhaust goes to the boiler producing 2,917 kg of steam per hour. That is why a plant first determines how much steam it needs, and only then calculates how much heat is left for cooling. More: trigeneration for pharmaceuticals.
How does this kind of scheme work?
The heat recovery steam generator produces steam. In the diagram, steam also goes to a steam-fired chiller; here the cooling comes from chillers running on exhaust and jacket water, and the steam goes to the plant.
Based on Thermax materials
Other projects worldwide

AT&S in Shanghai: one 1.1 MW engine and one Thermax absorption chiller give 1,160 kW of cooling in summer and 80 °C hot water in…

Berlin Airport: two Thermax chillers on engine exhaust give 2,600 kW of air conditioning cooling. A trigeneration case with…

Brevoort East residential building in New York: two Tecogen engines and a 280 kW Thermax machine that kept running through…
What our customers say
150 letters of thanks · 350+ major projects · 1,000+ customers · in business since 2011. These are real letters from customers; many others are on the references page.
Let us calculate trigeneration for your site
An engineer will put together the scheme and select the equipment, and you get a feasibility study. Free of charge, no obligation.