HuaiNan (Panyi) Coal Mine, China

In brief. Coal mine methane fuels two Deutz engines, and their exhaust and jacket heat becomes 3,023 kW of cooling for the mine at 1,000 m.

HuaiNan (Panyi) Coal Mine, China

At the HuaiNan coal mine, two 1.4 MW Deutz engines run on coal mine methane. All of the exhaust and jacket heat goes to a single 3,023 kW Thermax absorption chiller, which air-conditions the mine at a depth of 1,000 m.

What does the project consist of?

Parameter Value
Industry Coal mining
Engines 2 Deutz engines, 1.4 MW each
Fuel Coal mine methane
Heat for the chiller Exhaust at 525 °C and jacket water at 85 °C
Chillers and cooling 1 chiller, 3,023 kW (860 TR)
What the cooling is for Air conditioning of the mine at a depth of 1,000 m

Why is this example useful for a Russian site?

Exhaust and jacket heat from two 1.4 MW engines give 3,023 kW of cooling. If the chiller sits on the surface and the cooling is needed at a depth of 1,000 m, the water column creates about 100 bar, while the chiller is rated for 8 kgf/cm². The circuits must be separated by a heat exchanger. For a Russian mine this is the first check, even before the methane calculation. More: biogas, coal mine gas and associated petroleum gas.

How does this kind of scheme work?

Mine gas fuels the engine, and its heat is turned into cooling.

Biogas goes into a gas engine after cleaning. Part of the heat returns to the digester, the rest goes into a Thermax chiller. Heat that would otherwise be lost produces cooling.

Based on Thermax materials

What our customers say

150 letters of thanks · 350+ major projects · 1,000+ customers · in business since 2011. These are real letters from customers; many others are on the references page.

All references and letters All projects

Let us calculate trigeneration for your site

An engineer will put together the scheme and select the equipment, and you get a feasibility study. Free of charge, no obligation.

Get a feasibility study